Skip to content

Cat C18 | DE850E0 diesel generator set

Full Technical Information

Open PDF Specification

Overview, Engine and Ratings

Bore x Stroke
145 mm x 183 mm (5.7in x 7.2in)
Displacement
18.13 L (1106.3 in³)
Compression Ratio
14:1
Governor
Electronic ADEM™ A4 – G3 Class* capable

Package Performance

Details
Performance StandbyPrime
Frequency 50 Hz
Genset Power Rating 850 kVA770 kVA
Genset power rating with fan @ 0.8 power factor 680 ekW616 ekW
100% load with fan, L/hr (gal/hr) 175.7 (46.4)158 (41.7)
75% load with fan, L/hr (gal/hr) 128.3 (33.8)115 (30.3)
50% load with fan, L/hr (gal/hr) 86.5 (22.8)80 (21.1)
25% load with fan, L/hr (gal/hr) 47 (12.4)46.6 (12.3)
Radiator air flow restriction (system), kPa (in. water) 0.12 (0.48)0.12 (0.48)
Engine coolant capacity, L (gal) 21 (5.5)21 (5.5)
Radiator coolant capacity, L (gal) 86.5 (23.5)89 (23.5)
Total coolant capacity, L (gal) 110 (29.1)110 (29.1)
Combustion air inlet flow rate, m³/min (CFM) 62 (2189)58.2 (2055)
Max. Allowable Combustion Air Inlet Temp, °C (°F) 3.7 (clean element) / 6.2 (dirty element)
Exhaust stack gas temperature, °C (°F) 423 (793)404 (759)
Exhaust gas flow rate, m³/min (CFM) 147 (5191)134 (4732)
Exhaust system backpressure (maximum allowable) kPa (in. water) 10 (40.1)10 (40.1)
Heat rejection to jacket water, kW (BTU/min) 198 (11260)176 (10009)
Heat rejection to exhaust (total) kW (BTU/min) 624 (35486)565 (32131)
Heat rejection to aftercooler, kW (BTU/min) 231 (13136)203 (11544)
Heat rejection to atmosphere from engine, kW (BTU/min) 109 (6198)96 (5459)
Emissions (Nominal) 2
NOx, mg/Nm³ (g/hp-hr) 2748 (6.01)2751.3 (5.96)
CO, mg/Nm³ (g/hp-hr) 1000.6 (2.19)501.7 (1.09)
HC, mg/Nm³ (g/hp-hr) 66.4 (0.17)26.5 (0.09)
PM, mg/Nm³ (g/hp-hr) 70.2 (0.18)68.3 (0.1)
Voltages 415 V400 V380 V415 V400 V380 V
Motor starting capability @ 30% Voltage Dip & 0.6 P.F 2268 skVA2118 skVA1924 skVA2268 skVA2118 skVA1924 skVA
Temperature Rise 150°C150°C150°C125°C125°C125°C

Weights and Dimensions

Length
4,130 mm (163 in)
Width
1,689 mm (67 in)
Height
2,570 mm (101 in)
Weight
4,532 kg (9,991 lb)
Details

Note: General configuration not to be used for installation. See general dimension drawings for detail.

Applicable Codes and Standards

Details
AS1359, IEC60034-1, ISO 3046, ISO 8528, NEMA MG1-33, EAC, CE, UKCA. 1
normal source power. Average power output is 70% of the standby power rating. Typical Data shown is based on steady state operating conditions of 77° F, 28.42 in HG and
ekW with 10% overload capability for emergency use for a maximum of 1 hour in 12. 3

Commercial Application

Standby and prime power for buildings, manufacturing, data centers and distributed infrastructure. The card helps quickly verify configuration, frequency, power, dimensions and delivery availability for a specific site.