Cat D600 GC diesel generator set
Full Technical Information
Open PDF SpecificationOverview, Engine and Ratings
- Bore x Stroke
- 145 mm x 183 mm (5.7 in x 7.2 in)
- Displacement
- 18.1 L (1106 in³)
- Compression Ratio
- 14.5:1
- Governor
- Electronic ADEM™ A4 – G3 Class* capable
Package Performance
Details
Performance
StandbyPrime
Frequency
60 Hz
Genset Power Rating
750 kVA681 kVA
Genset power rating with fan @ 0.8 power factor
600 ekW545 ekW
Emissions
EPA TIER 2
100% load with fan, L/hr (gal/hr)
157.2 (40.3)147.0 (38.8)
75% load with fan, L/hr (gal/hr)
126.1 (33.3)120.2 (31.7)
50% load with fan, L/hr (gal/hr)
89.2 (23.5)86.7 (22.9)
25% load with fan, L/hr (gal/hr)
45.5 (12.0)47.4 (12.5)
Radiator air flow restriction (system), kPa (in water)
0.12 (0.48)
Radiator air flow, m3/min (CFM)
704 (24861)
Engine coolant capacity, L (gal)
20.8 (5.5)
Radiator coolant capacity, L (gal)
61 (16)
Total coolant capacity, L (gal)
82 (22)
Combustion air inlet flow rate m3/min (CFM)
47.8 (1688)46.7 (1688)
Max. allowable combustion air inlet temp, °C (°F)
49 (122)49 (122)
Exhaust stack gas temperature, °C (°F)
535 (994)518 (964)
Exhaust gas flow rate, m³/min (CFM)
135.5 (4784.4)129.6 (4577)
Exhaust system backpressure (maximum allowable) kPa (in. water)
10.0 (40.0)
Heat rejection to jacket water, kW (BTU/min)
189 (10748)175 (9952)
Heat rejection to exhaust (total), kW (BTU/min)
634 (36055)596 (33893)
Heat rejection to aftercooler, kW (BTU/min)
153 (8700)142 (8075)
Heat rejection to atmosphere from engine, kW (BTU/min)
86.2 (4902)83.1 (4726)
Heat rejection from alternator, kW (BTU/min)
33 (1876)31 (1763)
NOx, mg/Nm³ (g/hp-hr)
2798.7 (5.75)2462.2 (5.10)
CO, mg/Nm³ (g/hp-hr)
225.2 (0.46)195.1 (0.4)
HC, mg/Nm³ (g/hp-hr)
3.8 (0.01)5.0 (0.01)
PM, mg/Nm³ (g/hp-hr)
13.3 (0.03)13.1 (0.03)
Voltages
480V600V480V600V
Motor starting capability @ 30% Voltage Dip, skVA
1438149414381494
Current Amps
902722819656
Temperature Rise, °C
105130105130
Weights and Dimensions
- Length
- 4,980 mm (196.1 in)
- Width
- 1,865 mm (73.4 in)
- Height
- 2,009 mm (79.1 in)
- Weight
- 4,064 kg (8,960 lb)
Details
Note: General configuration not to be used for installation. See general dimension drawings for detail.
Applicable Codes and Standards
Details
CSA C22.2 No 100-04, UL489, UL869, UL2200, IBC, IEC60034-1, ISO 3046, ISO 8528,
1
normal source power. Average power output is 70% of the standby power rating. Typical
data shown is subject to instrumentation, measurement, facility and engine to engine
output is 70% of the prime power rating. Typical peak demand is 100% of prime rated
3
RATINGS: Ratings are based on SAE J1349 standard conditions. These ratings also
Governing Class capability as per ISO 8528-5. Consult your local Cat dealer for
Commercial Application
Standby and prime power for buildings, manufacturing, data centers and distributed infrastructure. The card helps quickly verify configuration, frequency, power, dimensions and delivery availability for a specific site.