Cat C18 | DE715E0 diesel generator set
Power Ratings
| Rating | kVA | ekW |
|---|---|---|
| Standby | 715 kVA | 572 ekW |
| Prime | 650 kVA | 520 ekW |
Full Technical Information
Open PDF SpecificationOverview, Engine and Ratings
- Bore x Stroke
- 145 mm x 183 mm (5.7in x 7.2in)
- Displacement
- 18.1 L (1106 in³)
- Compression Ratio
- 14.5:1
- Governor
- Electronic ADEM™ A4 – G3 Class* capable
Package Performance
Details
Performance
StandbyPrime
Frequency
50 Hz
Genset Power Rating
715 kVA650 kVA
Genset power rating with fan @ 0.8 power factor
572 ekW520 ekW
100% load with fan, L/hr (gal/hr)
144.2 (31.7)131.4 (28.9)
75% load with fan, L/hr (gal/hr)
106.6 (23.5)97.1 (21.4)
50% load with fan, L/hr (gal/hr)
72.2 (15.9)66.3 (14.6)
25% load with fan, L/hr (gal/hr)
40.5 (8.9)37.5 (8.2)
Radiator air flow restriction (system), kPa (in. water)
0.12 (0.48)0.12 (0.48)
Engine coolant capacity, L (gal)
20.8 (5.5)20.8 (5.5)
Radiator coolant capacity, L (gal)
34 (8.9)34 (8.9)
Total coolant capacity, L (gal)
54.8 (14.4)54.8 (14.4)
Combustion air inlet flow rate, m³/min (CFM)
37.5 (1325.8)35.3 (1246.1)
Max. Allowable Combustion Air Inlet Temp, °C (°F)
51 (124)49 (119)
Exhaust stack gas temperature, °C (°F)
568.2 (1054.8)550.5 (1022.9)
Exhaust gas flow rate, m³/min (CFM)
110.6 (3906.1)101.2 (3572.0)
Exhaust system backpressure (maximum allowable) kPa (in. water)
10.0 (40.0)10.0 (40.0)
Heat rejection to jacket water, kW (BTU/min)
179 (10181)165 (9375)
Heat rejection to exhaust (total) kW (BTU/min)
541 (30791)487 (27711)
Heat rejection to aftercooler, kW (BTU/min)
107 (6091)91 (5192)
Heat rejection to atmosphere from engine, kW (BTU/min)
89 (5064)83 (4729)
Emissions (Nominal)
2
NOx, mg/Nm³ (g/hp-hr)
2989.7 (6.1)3135.1 (6.2)
CO, mg/Nm³ (g/hp-hr)
354.8 (0.7)411.8 (0.8)
HC, mg/Nm³ (g/hp-hr)
4.3 (0.0)7.2 (0.0)
PM, mg/Nm³ (g/hp-hr)
9.4 (0.0)14.2 (0.0)
Voltages
380V400V415V
Motor starting capability @ 30% Voltage Dip & 0.6 P.F
1859 skVA2064 skVA2228 skVA
Temperature Rise, °C
SB: 163, PP: 125
Weights and Dimensions
- Length
- 3,910 mm (154 in)
- Width
- 1,461 mm (58 in)
- Height
- 2,156 mm (85 in)
- Weight
- 4,143 kg (9,134 lb)
Details
Note: General configuration not to be used for installation. See general dimension drawings for detail.
Applicable Codes and Standards
Details
AS1359, IEC60034-1, ISO 3046, ISO 8528, NEMA MG1-33, EAC, CE, UKCA.
1
normal source power. Average power output is 70% of the standby power rating. Typical
Data shown is based on steady state operating conditions of 77° F, 28.42 in HG and
ekW with 10% overload capability for emergency use for a maximum of 1 hour in 12.
3
Commercial Application
Standby and prime power for buildings, manufacturing, data centers and distributed infrastructure. The card helps quickly verify configuration, frequency, power, dimensions and delivery availability for a specific site.