Skip to content

Cat C18 | DE715E0 diesel generator set

Power Ratings

RatingkVAekW
Standby715 kVA572 ekW
Prime650 kVA520 ekW

Full Technical Information

Open PDF Specification

Overview, Engine and Ratings

Bore x Stroke
145 mm x 183 mm (5.7in x 7.2in)
Displacement
18.1 L (1106 in³)
Compression Ratio
14.5:1
Governor
Electronic ADEM™ A4 – G3 Class* capable

Package Performance

Details
Performance StandbyPrime
Frequency 50 Hz
Genset Power Rating 715 kVA650 kVA
Genset power rating with fan @ 0.8 power factor 572 ekW520 ekW
100% load with fan, L/hr (gal/hr) 144.2 (31.7)131.4 (28.9)
75% load with fan, L/hr (gal/hr) 106.6 (23.5)97.1 (21.4)
50% load with fan, L/hr (gal/hr) 72.2 (15.9)66.3 (14.6)
25% load with fan, L/hr (gal/hr) 40.5 (8.9)37.5 (8.2)
Radiator air flow restriction (system), kPa (in. water) 0.12 (0.48)0.12 (0.48)
Engine coolant capacity, L (gal) 20.8 (5.5)20.8 (5.5)
Radiator coolant capacity, L (gal) 34 (8.9)34 (8.9)
Total coolant capacity, L (gal) 54.8 (14.4)54.8 (14.4)
Combustion air inlet flow rate, m³/min (CFM) 37.5 (1325.8)35.3 (1246.1)
Max. Allowable Combustion Air Inlet Temp, °C (°F) 51 (124)49 (119)
Exhaust stack gas temperature, °C (°F) 568.2 (1054.8)550.5 (1022.9)
Exhaust gas flow rate, m³/min (CFM) 110.6 (3906.1)101.2 (3572.0)
Exhaust system backpressure (maximum allowable) kPa (in. water) 10.0 (40.0)10.0 (40.0)
Heat rejection to jacket water, kW (BTU/min) 179 (10181)165 (9375)
Heat rejection to exhaust (total) kW (BTU/min) 541 (30791)487 (27711)
Heat rejection to aftercooler, kW (BTU/min) 107 (6091)91 (5192)
Heat rejection to atmosphere from engine, kW (BTU/min) 89 (5064)83 (4729)
Emissions (Nominal) 2
NOx, mg/Nm³ (g/hp-hr) 2989.7 (6.1)3135.1 (6.2)
CO, mg/Nm³ (g/hp-hr) 354.8 (0.7)411.8 (0.8)
HC, mg/Nm³ (g/hp-hr) 4.3 (0.0)7.2 (0.0)
PM, mg/Nm³ (g/hp-hr) 9.4 (0.0)14.2 (0.0)
Voltages 380V400V415V
Motor starting capability @ 30% Voltage Dip & 0.6 P.F 1859 skVA2064 skVA2228 skVA
Temperature Rise, °C SB: 163, PP: 125

Weights and Dimensions

Length
3,910 mm (154 in)
Width
1,461 mm (58 in)
Height
2,156 mm (85 in)
Weight
4,143 kg (9,134 lb)
Details

Note: General configuration not to be used for installation. See general dimension drawings for detail.

Applicable Codes and Standards

Details
AS1359, IEC60034-1, ISO 3046, ISO 8528, NEMA MG1-33, EAC, CE, UKCA. 1
normal source power. Average power output is 70% of the standby power rating. Typical Data shown is based on steady state operating conditions of 77° F, 28.42 in HG and
ekW with 10% overload capability for emergency use for a maximum of 1 hour in 12. 3

Commercial Application

Standby and prime power for buildings, manufacturing, data centers and distributed infrastructure. The card helps quickly verify configuration, frequency, power, dimensions and delivery availability for a specific site.