Cat C18 | DE660E0 diesel generator set
Power Ratings
| Rating | kVA | ekW |
|---|---|---|
| Standby | 660 kVA | 528 ekW |
| Prime | 600 kVA | 480 ekW |
Full Technical Information
Open PDF SpecificationOverview, Engine and Ratings
- Bore x Stroke
- 145mm x 183mm (5.7in x 7.2in)
- Displacement
- 18.1 L ( 1106 in3)
- Compression Ratio
- 14.5:1
- Governor
- Electronic ADEM™ A4 - G3 Class* capable
Package Performance
Details
Performance
StandbyPrime
Frequency
50 Hz
Genset Power Rating
660 kVA600 kVA
Genset power rating with fan @ 0.8 power factor
528 ekW480 ekW
100% load with fan, L/hr (gal/hr)
135.0 (35.7)122.7 (32.4)
75% load with fan, L/hr (gal/hr)
100.9 (26.7)91.9 (24.3)
50% load with fan, L/hr (gal/hr)
69.5 (18.3)63.9 (16.9)
25% load with fan, L/hr (gal/hr)
40.1 (10.6)37.3 (9.8)
Radiator air flow restriction (system), kPa (in. water)
0.12 (0.48)0.12 (0.48)
Radiator air flow, m3/min (cfm)
373 (13172)373 (13172)
Engine coolant capacity, L (gal)
20.8 (5.5)20.8 (5.5)
Radiator coolant capacity, L (gal)
34 (8.9)34 (8.9)
Total coolant capacity, L (gal)
54.8 (14.4)54.8 (14.4)
Combustion air inlet flow rate, m³/min (cfm)
34.2 (1206.4)32.3 (1142.0)
Max. Allowable Combustion Air Inlet Temp, °C (°F)
49 (121)47 (117)
Exhaust stack gas temperature, °C (°F)
571.1 (1060.0)555.6 (1032.0)
Exhaust gas flow rate, m³/min (cfm)
102.4 (3614.4)94.3 (3329.2)
Exhaust system back pressure (maximum allowable), kPa (in. water)
10.0 (40.0)10.0 (40.0)
Heat rejection to jacket water, kW (Btu/min)
169 (9625)157 (8947)
Heat rejection to exhaust (total), kW (Btu/min)
504 (28661)458 (26037)
Heat rejection to aftercooler, kW (Btu/min)
91 (5186)79 (4475)
Heat rejection to atmosphere from engine, kW (Btu/min)
84 (4787)79 (4468)
NOx, mg/Nm³ (g/hp-hr)
3486.4 (7.0)3490.3 (6.9)
CO, mg/Nm³ (g/hp-hr)
507.4 (1.0)506.5 (1.0)
HC, mg/Nm³ (g/hp-hr)
1.7 (0.0)2.6 (0.0)
PM, mg/Nm³ (g/hp-hr)
4.7 (0.0)4.7 (0.0)
Voltages
380V400V415V
Motor starting capability @ 30% Voltage Dip
1564 skVA1739 skVA1869 skVA
Temperature Rise
SB: 163°C, PP: 125°C
Weights and Dimensions
- Length
- 3,910 mm (154 in)
- Width
- 1,461 mm (58 in)
- Height
- 2,156 mm (85 in)
- Weight
- 3,862 kg (8,514 lb)
Details
Note: General configuration not to be used for installation. See general dimension drawings for detail.
Applicable Codes and Standards
Details
AS1359, IEC60034-1, ISO3046, ISO8528, NEMA MG1-33, UKCA, CE, EAC.
1
interruption of the normal source power. Average power output is 70% of the
NOx. Data shown is based on steady state operating conditions of 77° F, 28.42
standby power rating. Typical operation is 200 hours per year, with maximum
in HG and number 2 diesel fuel with 35° API and LHV of 18,390 BTU/lb. The
hour in 12. Overload operation cannot exceed 25 hours per year
3
RATINGS: Ratings are based on SAE J1349 standard conditions. These ratings
Governing Class capability as per ISO8528-5.Consult your local Cat dealer for
Commercial Application
Standby and prime power for buildings, manufacturing, data centers and distributed infrastructure. The card helps quickly verify configuration, frequency, power, dimensions and delivery availability for a specific site.