Cat C18 | DE660E0 diesel generator set

Power Ratings

RatingkVAekW
Standby660 kVA528 ekW
Prime600 kVA480 ekW

Full Technical Information

Open PDF Specification

Overview, Engine and Ratings

Bore x Stroke
145mm x 183mm (5.7in x 7.2in)
Displacement
18.1 L ( 1106 in3)
Compression Ratio
14.5:1
Governor
Electronic ADEM™ A4 - G3 Class* capable

Package Performance

Details
Performance StandbyPrime
Frequency 50 Hz
Genset Power Rating 660 kVA600 kVA
Genset power rating with fan @ 0.8 power factor 528 ekW480 ekW
100% load with fan, L/hr (gal/hr) 135.0 (35.7)122.7 (32.4)
75% load with fan, L/hr (gal/hr) 100.9 (26.7)91.9 (24.3)
50% load with fan, L/hr (gal/hr) 69.5 (18.3)63.9 (16.9)
25% load with fan, L/hr (gal/hr) 40.1 (10.6)37.3 (9.8)
Radiator air flow restriction (system), kPa (in. water) 0.12 (0.48)0.12 (0.48)
Radiator air flow, m3/min (cfm) 373 (13172)373 (13172)
Engine coolant capacity, L (gal) 20.8 (5.5)20.8 (5.5)
Radiator coolant capacity, L (gal) 34 (8.9)34 (8.9)
Total coolant capacity, L (gal) 54.8 (14.4)54.8 (14.4)
Combustion air inlet flow rate, m³/min (cfm) 34.2 (1206.4)32.3 (1142.0)
Max. Allowable Combustion Air Inlet Temp, °C (°F) 49 (121)47 (117)
Exhaust stack gas temperature, °C (°F) 571.1 (1060.0)555.6 (1032.0)
Exhaust gas flow rate, m³/min (cfm) 102.4 (3614.4)94.3 (3329.2)
Exhaust system back pressure (maximum allowable), kPa (in. water) 10.0 (40.0)10.0 (40.0)
Heat rejection to jacket water, kW (Btu/min) 169 (9625)157 (8947)
Heat rejection to exhaust (total), kW (Btu/min) 504 (28661)458 (26037)
Heat rejection to aftercooler, kW (Btu/min) 91 (5186)79 (4475)
Heat rejection to atmosphere from engine, kW (Btu/min) 84 (4787)79 (4468)
NOx, mg/Nm³ (g/hp-hr) 3486.4 (7.0)3490.3 (6.9)
CO, mg/Nm³ (g/hp-hr) 507.4 (1.0)506.5 (1.0)
HC, mg/Nm³ (g/hp-hr) 1.7 (0.0)2.6 (0.0)
PM, mg/Nm³ (g/hp-hr) 4.7 (0.0)4.7 (0.0)
Voltages 380V400V415V
Motor starting capability @ 30% Voltage Dip 1564 skVA1739 skVA1869 skVA
Temperature Rise SB: 163°C, PP: 125°C

Weights and Dimensions

Length
3,910 mm (154 in)
Width
1,461 mm (58 in)
Height
2,156 mm (85 in)
Weight
3,862 kg (8,514 lb)
Details

Note: General configuration not to be used for installation. See general dimension drawings for detail.

Applicable Codes and Standards

Details
AS1359, IEC60034-1, ISO3046, ISO8528, NEMA MG1-33, UKCA, CE, EAC. 1
interruption of the normal source power. Average power output is 70% of the NOx. Data shown is based on steady state operating conditions of 77° F, 28.42
standby power rating. Typical operation is 200 hours per year, with maximum in HG and number 2 diesel fuel with 35° API and LHV of 18,390 BTU/lb. The
hour in 12. Overload operation cannot exceed 25 hours per year 3
RATINGS: Ratings are based on SAE J1349 standard conditions. These ratings Governing Class capability as per ISO8528-5.Consult your local Cat dealer for

Commercial Application

Standby and prime power for buildings, manufacturing, data centers and distributed infrastructure. The card helps quickly verify configuration, frequency, power, dimensions and delivery availability for a specific site.