Power Ratings

RatingkVAekW
Standby625 kVA500 ekW
Prime569 kVA455 ekW

Full Technical Information

Open PDF Specification

Overview, Engine and Ratings

Bore x Stroke
137mm x 171mm (5.4in x 6.8in)
Displacement
15.2 L (928 in³)
Compression Ratio
16.1:1
Governor
Electronic ADEM™ A4 - G3 Class* capable

Package Performance

Details
Performance StandbyPrime
Frequency 60 Hz
Genset Power Rating 625 kVA569 kVA
Genset power rating with fan @ 0.8 power factor 500 ekW455 ekW
100% load with fan, L/hr (gal/hr) 127.2 (33.6)117.3 (31.0)
75% load with fan, L/hr (gal/hr) 98.3 (26.0)90.4 (23.9)
50% load with fan, L/hr (gal/hr) 69.8 (18.4)64.6 (17.1)
25% load with fan, L/hr (gal/hr) 41.7 (11.0)39.1 (10.3)
Radiator air flow restriction (system), kPa (in. water) 0.12 (0.48)0.12 (0.48)
Radiator air flow, m3/min (cfm) 659 (23272)659 (23272)
Engine coolant capacity, L (gal) 20.8 (5.5)20.8 (5.5)
Radiator coolant capacity, L (gal) 37 (9.7)37 (9.7)
Total coolant capacity, L (gal) 57.8 (15.2)57.8 (15.2)
Combustion air inlet flow rate, m³/min (cfm) 37.9 (1337.4)35.2 (1241.5)
Max. Allowable Combustion Air Inlet Temp, °C (°F) 47 (117)43 (110)
Exhaust stack gas temperature, °C (°F) 510.3 (950.6)505.4 (941.7)
Exhaust gas flow rate, m³/min (cfm) 102.7 (3627.4)94.2 (3327.5)
Exhaust system back pressure (maximum allowable), kPa (in. water) 10.0 (40.0)10.0 (40.0)
Heat rejection to jacket water, kW (Btu/min) 185 (10501)180 (10224)
Heat rejection to exhaust (total), kW (Btu/min) 477 (27109)436 (24783)
Heat rejection to aftercooler, kW (Btu/min) 108 (6125)91 (5186)
Heat rejection to atmosphere from engine, kW (Btu/min) 13 (767)22 (1244)
LEHE1640-02 1/2
NOx, mg/Nm³ (g/hp-hr) 3377.5 (6.6)3329.0 (6.6)
CO, mg/Nm³ (g/hp-hr) 197.8 (0.4)186.1 (0.4)
HC, mg/Nm³ (g/hp-hr) 3.0 (0.0)2.8 (0.0)
PM, mg/Nm³ (g/hp-hr) 3.0 (0.0)11.1 (0.0)
Voltages 220V240V380V440V480V
1305 skVA 1553 skVA971 skVA1305 skVA1553 skVA
Temperature Rise SB: 163°C, PP: 125°C

Weights and Dimensions

Length
3,830 mm (151 in)
Width
1,130 mm (44 in)
Height
2,255 mm (89 in)
Weight
3,700 kg (8,157 lb)
Details

Note: General configuration not to be used for installation. See general dimension drawings for detail.

Applicable Codes and Standards

Details
AS1359, IEC60034-1, ISO3046, ISO8528, NEMA MG1-33, EAC,CE,UKCA. 1
interruption of the normal source power. Average power output is 70% of the in HG and number 2 diesel fuel with 35° API and LHV of 18,390 BTU/lb. The
standby power rating. Typical operation is 200 hours per year, with maximum nominal emissions data shown is subject to instrumentation, measurement,
rated ekW with 10% overload capability for emergency use for a maximum of 1 3
hour in 12. Overload operation cannot exceed 25 hours per year Governing Class capability as per ISO8528-5.Consult your local Cat dealer for

Commercial Application

Standby and prime power for buildings, manufacturing, data centers and distributed infrastructure. The card helps quickly verify configuration, frequency, power, dimensions and delivery availability for a specific site.