Cat C18 | DE780E0 diesel generator set
Full Technical Information
Open PDF SpecificationOverview, Engine and Ratings
- Bore x Stroke
- 145 mm x 183 mm (5.7 in x 7.2 in)
- Displacement
- 18.13 L (1106.3 in³)
- Compression Ratio
- 14:1
- Governor
- Electronic ADEM™ A4 – G3 Class* capable
Package Performance
Details
Performance
StandbyPrime
Frequency
50 Hz
Genset Power Rating
780 kVA706 kVA
Genset power rating with fan @ 0.8 power factor
624 ekW564 ekW
100% load with fan, L/hr (gal/hr)
157 (41.4)142.1 (37.5)
75% load with fan, L/hr (gal/hr)
116.3 (30.7)105.2 (27.7)
50% load with fan, L/hr (gal/hr)
80.5 (21.2)74.1 (19.5)
25% load with fan, L/hr (gal/hr)
46.9 (12.3)43.7 (11.5)
Radiator air flow restriction (system), kPa (in. water)
0.12 (0.48)0.12 (0.48)
Engine coolant capacity, L (gal)
21 (5.5)21 (5.5)
Radiator coolant capacity, L (gal)
89 (23.5)89 (23.5)
Total coolant capacity, L (gal)
110 (29.1)110 (29.1)
Combustion air inlet flow rate, m³/min (CFM)
56 (1977)52.4 (1850)
Max. Allowable Combustion Air Inlet Temp, °C (°F)
3.7 (clean element) / 6.2 (dirty element)
Exhaust stack gas temperature, °C (°F)
406 (762)394 (741)
Exhaust gas flow rate, m³/min (CFM)
131 (4662)120 (4202)
Exhaust system backpressure (maximum allowable) kPa (in. water)
10 (40.1)10 (40.1)
Heat rejection to jacket water, kW (BTU/min)
180 (10236)167 (9497)
Heat rejection to exhaust (total) kW (BTU/min)
553 (31449)497 (28264)
Heat rejection to aftercooler, kW (BTU/min)
192 10919)170 (9667)
Heat rejection to atmosphere from engine, kW (BTU/min)
91.1 (5180)85 (4833)
Emissions (Nominal)
2
NOx, mg/Nm³ (g/hp-hr)
3080.2 (6.54)2988 (6.31)
CO, mg/Nm³ (g/hp-hr)
161.9 (0.35)82.6 (0.17)
HC, mg/Nm³ (g/hp-hr)
31.8 (0.08)14 (0.03)
PM, mg/Nm³ (g/hp-hr)
11.3 (0.03)9.3 (0.02)
Voltages
415 V400 V380 V415 V400 V380 V
Motor starting capability @ 30% Voltage Dip & 0.6 P.F
2278 skVA2128 skVA1935 skVA2278 skVA2128 skVA1935 skVA
Temperature Rise
163°C150°C163°C125°C125°C125°C
Weights and Dimensions
- Length
- 4,130 mm (163 in)
- Width
- 1,689 mm (67 in)
- Height
- 2,570 mm (101 in)
- Weight
- 4,532 kg (9,991 lb)
Details
Note: General configuration not to be used for installation. See general dimension drawings for detail.
Applicable Codes and Standards
Details
AS1359, IEC60034-1, ISO 3046, ISO 8528, NEMA MG1-33, EAC, CE, UKCA.
1
normal source power. Average power output is 70% of the standby power rating. Typical
Data shown is based on steady state operating conditions of 77° F, 28.42 in HG and
ekW with 10% overload capability for emergency use for a maximum of 1 hour in 12.
3
Commercial Application
Standby and prime power for buildings, manufacturing, data centers and distributed infrastructure. The card helps quickly verify configuration, frequency, power, dimensions and delivery availability for a specific site.



