Skip to content

Cat C18 (60 Hz) diesel generator set

Full Technical Information

Open PDF Specification

Overview, Engine and Ratings

Bore x Stroke
145 mm x 183 mm (5.7 in x 7.2 in)
Displacement
18.13 L (1106.3 in³)
Compression Ratio
14:1
Governor
Electronic ADEM™ A4 – G3 Class* capable

Package Performance

Details
Performance StandbyPrime
Frequency 60 Hz
Genset Power Rating 938 kVA850 kVA
Genset power rating with fan @ 0.8 power factor 750 ekW680 ekW
100% load with fan, L/hr (gal/hr) 200.8 (53.0)184.3 (48.4)
75% load with fan, L/hr (gal/hr) 160.6 (42.4)143.0 (37.7)
50% load with fan, L/hr (gal/hr) 106.5 (28.1)98.0 (25.8)
25% load with fan, L/hr (gal/hr) 62.1 (16.4)58.0 (15.3)
Radiator air flow restriction (system), kPa (in. water) 0.12 (0.48)0.12 (0.48)
Radiator air flow, m³/min (CFM) 900 (31783)900 (31783)
Engine coolant capacity, L (gal) 20.8 (5.5)20.8 (5.5)
Radiator coolant capacity, L (gal) 77 (20.3)77 (20.3)
Total coolant capacity, L (gal) 97.8 (25.8)97.8 (25.8)
Combustion air inlet flow rate, m³/min (CFM) 67.3 (2376)65.6 (2316)
Max. Allowable Combustion Air Inlet Temp, °C (°F) 49 (120)49 (120)
Exhaust stack gas temperature, °C (°F) 452.9 (847.2)432.9 (811.2)
Exhaust gas flow rate, m³/min (CFM) 170.7 (6028)161 (5686)
Exhaust system backpressure (maximum allowable), kPa (in. water) 10.0 (40.0)10.0 (40.0)
Heat rejection to jacket water, kW (BTU/min) 225 (12795)208 (11828)
Heat rejection to exhaust (total), kW (BTU/min) 714 (40604)664 (37761)
Heat rejection to aftercooler, kW (BTU/min) 272 (15468)253 (14387)
Heat rejection to atmosphere from engine, kW (BTU/min) 142 (8075)123 (6995)
Heat rejection from alternator, kW (BTU/min) 44.5 (2531)38.8 (2207)
NOx, mg/Nm³ (g/hp-hr) 2468 (5.42)2213 (4.91)
CO, mg/Nm³ (g/hp-hr) 100.1 (0.22)75.6 (0.17)
HC, mg/Nm³ (g/hp-hr) 23.5 (0.06)24.1 (0.06)
PM, mg/Nm³ (g/hp-hr) 11.7 (0.03)10.6 (0.03)
Duty Cycle StandbyPrime
Phase 3-Phase3-Phase
Voltages*, V 208220240480600208220240480600
Current, Amps 26022460225511289022359223120451022818

Weights and Dimensions

Length
3,512 mm (138 in)
Width
1,746 mm (69 in)
Height
2,322 mm (92 in)
Weight
4,863 kg (10,721 lb)
Details

Note: General configuration not to be used for installation. See general dimension drawings for detail.

Applicable Codes and Standards

Details
CSA C22.2 No 100-04, UL489, UL869, UL2200, IBC, IEC60034-1, ISO 3046, ISO 8528, 1

Commercial Application

Standby and prime power for buildings, manufacturing, data centers and distributed infrastructure. The card helps quickly verify configuration, frequency, power, dimensions and delivery availability for a specific site.