Skip to content

Cat D250 GC diesel generator set

Full Technical Information

Open PDF Specification

Overview, Engine and Ratings

Bore x Stroke
112 mm x 149 mm (4.4 in x 5.9 in)
Displacement
8.8 L (538 in³)
Compression Ratio
16.3:1
Governor
Electronic ADEM™ A4 - G2 Class* capable

Package Performance

Details
Performance Standby
Frequency 60 Hz
Genset Power Rating 312.5 kVA
Genset power rating with fan @ 0.8 pf 250 ekW
Emissions EPA TIER 3
100% load with fan, L/hr (gal/hr) 73.3 (19.4)
75% load with fan, L/hr (gal/hr) 58.8 (15.5)
50% load with fan, L/hr (gal/hr) 43.8 (11.6)
25% load with fan, L/hr (gal/hr) 27.4 (7.3)
Radiator air flow restriction (system), kPa (in water) 0.12 (0.48)
Radiator air flow, m3/min (CFM) 497 (17551)
Engine coolant capacity, L (gal) 14 (3.69)
Radiator coolant capacity, L (gal) 25 (6.6)
Total coolant capacity, L (gal) 45 (11.88)
Combustion air inlet flow rate, m3/min (CFM) 23.83 (841.5)
Max. Allowable Combustion Air Inlet Temp, °C (°F) 49 (120)
Exhaust stack gas temperature, °C (°F) 460 (860)
Exhaust gas flow rate, m³/min (CFM) 63.6 (2246)
Exhaust system back pressure (maximum allowable), kPa (in. water) 10.0 (40.0)
Heat rejection to jacket water, kW (Btu/min) 104 (5928)
Heat rejection to exhaust (total), kW (Btu/min) 277 (15772)
Heat rejection to aftercooler, kW (Btu/min) 82 (4686)
Heat rejection to atmosphere from engine, kW (Btu/min) 18 (1004)
Heat rejection from alternator, kW (Btu/min) 20 (1120)
NOx, mg/Nm³ (g/hp-hr) 1637.5 (3.14)
CO, mg/Nm³ (g/hp-hr) 323.2 (0.68)
HC, mg/Nm³ (g/hp-hr) 71.2 (0.17)
PM, mg/Nm³ (g/hp-hr) 63.7 (0.16)
LEHE2023-04 1/2
Voltages 480V208600V
Motor starting capability @ 30% Voltage Dip, skVA 5675441006
Current, Amps 375.9867.4300.7
Temperature Rise, °C 105105105

Weights and Dimensions

Length
3,950 mm (155.5 in)
Width
1,440 mm (56.7 in)
Height
1,706 mm (67.2 in)
Weight
2,415 kg (5,324 lb)
Details

Note: General configuration not to be used for installation. See general dimension drawings for detail.

Applicable Codes and Standards

Details
CSA C22.2 No 100-04, UL142, UL489, UL869, cUL/UL2200, NFPA 37, 1
NEMA MG 1-33. 2
interruption of the normal source power. Average power output is 70% with 35° API and LHV of 18,390 BTU/lb. The nominal emissions data
having an LHV of 42 780 kJ/kg (18,390 Btu/lb) when used at 29º C temperature rise is based on a 40° C ambient per NEMA MG1-32.

Commercial Application

Standby and prime power for buildings, manufacturing, data centers and distributed infrastructure. The card helps quickly verify configuration, frequency, power, dimensions and delivery availability for a specific site.