Skip to content

Cat C9 | DE330E0 diesel generator set

Full Technical Information

Open PDF Specification

Overview, Engine and Ratings

Bore x Stroke
112 mm x 149 mm (4.4 in x 5.9 in)
Displacement
8.8 L (538 in³)
Compression Ratio
16.1:1
Governor
Electronic ADEM™ A4 – G3 Class* capable

Package Performance

Details
Performance StandbyPrime
Frequency 50 Hz
Genset Power Rating 330 kVA300 kVA
Genset power rating with fan @ 0.8 power factor 264 ekW240 ekW
100% load with fan, L/hr (gal/hr) 70.4 (18.6)60.5 (16)
75% load with fan, L/hr (gal/hr) 52.6 (13.9)48.8 (12.9)
50% load with fan, L/hr (gal/hr) 37 (9.8)35.9 (9.5)
25% load with fan, L/hr (gal/hr) 22.3 (5.9)20.8 (5.5)
Radiator air flow restriction (system), kPa (in. water) 0.12 (0.48)0.12 (0.48)
Radiator air flow, m3/min (CFM) 438 (14443)438 (14443)
Engine coolant capacity, L (gal) 13.9 (3.7)13.9 (3.7)
Radiator coolant capacity, L (gal) 43 (11.5)43 (11.5)
Total coolant capacity, L (gal) 56.9 (15.2)56.9 (15.2)
Combustion air inlet flow rate, m³/min (CFM) 17.5 (620)16.4 (581)
Max. Allowable Combustion Air Inlet Temp, °C (°F) 48 (118)48 (118)
Exhaust stack gas temperature, °C (°F) 575 (1067)545 (1012)
Exhaust gas flow rate, m³/min (CFM) 53.06 (1874)45.3 (1600)
Exhaust system backpressure (maximum allowable), kPa (in water) 10.0 (40.0)10.0 (40.0)
Heat rejection to jacket water, kW (BTU/min) 119 (6765)110 (6283)
Heat rejection to exhaust (total) kW (BTU/min) 245 (13944)220 (12517)
Heat rejection to aftercooler, kW (BTU/min) 37 (2121)45 (2552)
Heat rejection to atmosphere from engine, kW (BTU/min) 28 (1607)25.6 (1457)
NOx, mg/Nm³ (g/hp-hr) 2991 (6.06)3132 (6.52)
CO, mg/Nm³ (g/hp-hr) 824 (1.68)832.1 (1.75)
HC, mg/Nm³ (g/hp-hr) 14 (0.05)14.9 (0.04)
PM, mg/Nm³ (g/hp-hr) 29.1 (0.07)24.4 (0.06)
Voltages 230V380V400V415V
Motor starting capability @ 30% Voltage Dip 1205 skVA1081 skVA1205 skVA1296 skVA
Temperature Rise 125°C125°C125°C125°C

Weights and Dimensions

Length
2,662 mm (89 in)
Width
1,030 mm (41 in)
Height
1,754 mm (69 in)
Weight
2,261 kg (4,985 lb)
Details

Note: General configuration not to be used for installation. See general dimension drawings for detail.

Applicable Codes and Standards

Details
AS1359, IEC60034-1, ISO 3046, ISO 8528, NEMA MG1-33, EAC, CE, UKCA. 1
ekW with 10% overload capability for emergency use for a maximum of 1 hour in 12. 3

Commercial Application

Standby and prime power for buildings, manufacturing, data centers and distributed infrastructure. The card helps quickly verify configuration, frequency, power, dimensions and delivery availability for a specific site.