Overview, Engine and Ratings

Bore x Stroke
130 mm x 157 mm (5.1 in x 6.2 in)
Displacement
12.5 L (763 in³)
Compression Ratio
16.3:1
Governor
Electronic ADEM™ A4 - G3 Class* capable

Package Performance

Details
Performance Standby
Frequency 60 Hz
Genset Power Rating 437.50 kVA
Genset power rating with fan @ 0.8 pf 350 ekW
Emissions EPA TIER 3
100% load with fan, L/hr (gal/hr) 94.3 (24.9)
75% load with fan, L/hr (gal/hr) 81.9 (21.6)
50% load with fan, L/hr (gal/hr) 60.2 (15.9)
25% load with fan, L/hr (gal/hr) 34.3 (9.1)
Radiator air flow restriction (system), kPa (in water) 0.12 (0.48)
Radiator air flow, m3/min (CFM) 497 (17551)
Engine coolant capacity, L (gal) 14.2 (3.8)
Radiator coolant capacity, L (gal) 30 (8)
Total coolant capacity, L (gal) 34 (12)
Combustion air inlet flow rate m3/min (CFM) 24.8 (874.4)
Max. Allowable Combustion Air Inlet Temp, °C (°F) 49 (120)
Exhaust stack gas temperature, °C (°F) 571.2 (1060.1)
Exhaust gas flow rate, m³/min (CFM) 73.4 (2591.3)
Exhaust system backpressure (maximum allowable), kPa (in. water) 10.0 (40.0)
Heat rejection to jacket water, kW (Btu/min) 143 (8132)
Heat rejection to exhaust (total), kW (Btu/min) 360 (20484)
Heat rejection to aftercooler, kW (Btu/min) 55 (3108)
Heat rejection to atmosphere from engine, kW (Btu/min) 47 (2694)
Heat rejection from alternator, kW (Btu/min) 24 (1382)
NOx, mg/Nm³ (g/hp-hr) 2274.7 (4.58)
CO, mg/Nm³ (g/hp-hr) 666.9 (1.35)
HC, mg/Nm³ (g/hp-hr) 6.2 (0.01)
PM, mg/Nm³ (g/hp-hr) 39.4 (0.10)
LEHE2008-07 1/2
Voltages 480V600V
Motor starting capability @ 30% Voltage Dip, skVA 863951
Current, Amps 526.2421
Temperature Rise, °C 105105

Weights and Dimensions

Length
4,625 mm (182.8 in)
Width
1,630 mm (64.2 in)
Height
2,039 mm (80.3 in)
Weight
3,291 kg (7,255 lb)
Details

Note: General configuration not to be used for installation. See general dimension drawings for detail.

Applicable Codes and Standards

Details
AS1359, IEC60034-1, ISO3046, ISO8528, NEMA MG1-33, UKCA, CE, EAC. 1
normal source power. Average power output is 70% of the standby power rating. shown is based on steady state operating conditions of 77° F, 28.42 in HG and number
42 780 kJ/kg (18,390 Btu/lb) when used at 29º C (85º F) and weighing ambient per IEC60034-1

Commercial Application

Standby and prime power for buildings, manufacturing, data centers and distributed infrastructure. The card helps quickly verify configuration, frequency, power, dimensions and delivery availability for a specific site.