Cat C13 | DE450E0 diesel generator set
Full Technical Information
Open PDF SpecificationOverview, Engine and Ratings
- Bore x Stroke
- 130 mm x 157 mm (5.1 in x 6.2 in)
- Displacement
- 12.5 L (763 in³)
- Compression Ratio
- 16.3:1
- Governor
- Electronic ADEM™ A4 – G3 Class* capable
Package Performance
Details
Performance
StandbyPrime
Frequency
50 Hz
Genset Power Rating
450 kVA400 kVA
Genset power rating with fan @ 0.8 power factor
360 ekW320 ekW
100% load with fan, L/hr (gal/hr)
93.9 (24.8)82.9 (21.9)
75% load with fan, L/hr (gal/hr)
69.9 (18.5)62.2 (16.4)
50% load with fan, L/hr (gal/hr)
48.0 (12.7)43.3 (11.4)
25% load with fan, L/hr (gal/hr)
28.1 (7.4)25.8 (6.8)
Radiator air flow restriction (system), kPa (in. water)
0.12 (0.48)0.12 (0.48)
Radiator air flow, m3/min (CFM)
398 (14055)398 (14055)
Engine coolant capacity, L (gal)
13.9 (3.7)13.9 (3.7)
Radiator coolant capacity, L (gal)
43 (11.5)43 (11.5)
Total coolant capacity, L (gal)
56.9 (15.2)56.9 (15.2)
Combustion air inlet flow rate, m³/min (CFM)
24.7 (872)22.9 (807.9)
Max. Allowable Combustion Air Inlet Temp, °C (°F)
48 (118)44 (111)
Exhaust stack gas temperature, °C (°F)
531.1 (988)507.8 (946.0)
Exhaust gas flow rate, m³/min (CFM)
70.4 (2486)70.4 (2486)
Exhaust system backpressure (maximum allowable), kPa (in water)
10.0 (40.0)10.0 (40.0)
Heat rejection to jacket water, kW (BTU/min)
137 (7775)125 (7100)
Heat rejection to exhaust (total) kW (BTU/min)
326 (18562)288 (16381)
Heat rejection to aftercooler, kW (BTU/min)
71 (4014)58 (3302)
Heat rejection to atmosphere from engine, kW (BTU/min)
56 (3177)48 (2712)
NOx, mg/Nm³ (g/hp-hr)
2503.4 (4.9)2605.3 (5.1)
CO, mg/Nm³ (g/hp-hr)
702.2 (1.4)705.8 (1.4)
HC, mg/Nm³ (g/hp-hr)
3.1 (0.0)2.7 (0.0)
Voltages
415V400V380V
Motor starting capability @ 30% Voltage Dip
1202 skVA891 skVA1005 skVA
Temperature Rise
Standby: 163°C, Prime: 125°CStandby: 163°C, Prime: 125°CStandby: 163°C, Prime: 125°C
Weights and Dimensions
- Length
- 3,830 mm (151 in)
- Width
- 1,130 mm (44 in)
- Height
- 2,156 mm (85 in)
- Weight
- 3,253 kg (7,172 lb)
Details
Note: General configuration not to be used for installation. See general dimension drawings for detail.
Commercial Application
Standby and prime power for buildings, manufacturing, data centers and distributed infrastructure. The card helps quickly verify configuration, frequency, power, dimensions and delivery availability for a specific site.