Bore x Stroke
112 mm x 149 mm (4.4 in x 5.9 in)
Displacement
8.8 L (538 in³)
Compression Ratio
16.3:1
Governor
Electronic ADEM™ A4 – G3 Class* capable

Package Performance

Details
Performance Standby
Frequency 60 Hz
Genset Power Rating 375 kVA
Genset power rating with fan @ 0.8 power factor 300 ekW
Emissions EPA TIER 3
100% load with fan, L/hr (gal/hr) 84.1 (22.2)
75% load with fan, L/hr (gal/hr) 65.3 (17.25)
50% load with fan, L/hr (gal/hr) 50.3 (13.3)
25% load with fan, L/hr (gal/hr) 32.3 (8.5)
Radiator air flow restriction (system), kPa (in water) 0.12 (0.48)
Radiator air flow, m3/min (CFM) 600 (21188)
Engine coolant capacity, L (gal) 14 (3.69)
Radiator coolant capacity, L (gal) 25 (6.6)
Total coolant capacity, L (gal) 45 (11.88)
Combustion air inlet flow rate m3/min (CFM) 26 (918)
Max. Allowable Combustion Air Inlet Temp, °C (°F) 50.3 (122.5)
Exhaust stack gas temperature, °C (°F) 497 (926.6)
Exhaust gas flow rate, m³/min (CFM) 69.7 (2461)
Exhaust system backpressure (maximum allowable) kPa (in. water) 10.0 (40.0)
Heat rejection to jacket water, kW (BTU/min) 120 (6838)
Heat rejection to exhaust (total), kW (BTU/min) 320 (18223)
Heat rejection to aftercooler, kW (BTU/min) 92 (5239)
Heat rejection to atmosphere from engine, kW (BTU/min) 23 (1312)
Heat rejection from alternator, kW (BTU/min) 22 (1245)
NOx, mg/Nm³ (g/hp-hr) 2196.0 (4.00)
CO, mg/Nm³ (g/hp-hr) 115.5 (0.2)
HC, mg/Nm³ (g/hp-hr) 23.1 (0.06)
PM, mg/Nm³ (g/hp-hr) 12.7 (0.03)
Voltages 480V208600V
Motor starting capability @ 30% Voltage Dip, skVA 7055491117
Current Amps 4511041361
Temperature Rise, °C 105°C105°C105°C

Weights and Dimensions

Length
3,950 mm (155.5 in)
Width
1,440 mm (56.7 in)
Height
1,706 mm (67.2 in)
Weight
2,503 kg (5,518 lb)
Details

Note: General configuration not to be used for installation. See general dimension drawings for detail.

Applicable Codes and Standards

Details
CSA C22.2 No 100-04, UL489, UL869, UL2200, IBC, IEC60034-1, ISO 3046, ISO 8528, 1

Commercial Application

Standby and prime power for buildings, manufacturing, data centers and distributed infrastructure. The card helps quickly verify configuration, frequency, power, dimensions and delivery availability for a specific site.