Cat C13 | DE400E0 diesel generator set

Power Ratings

RatingkVAekW
Standby400 kVA320 ekW
Prime350 kVA280 ekW

Full Technical Information

Open PDF Specification

Overview, Engine and Ratings

Bore x Stroke
130 mm x 157 mm (5.1 in x 6.2 in)
Displacement
12.5 L (763 in³)
Compression Ratio
16.3:1
Governor
Electronic ADEM™ A4 – G3 Class* capable

Package Performance

Details
Performance StandbyPrime
Frequency 50 Hz
Genset Power Rating 400 kVA350 kVA
Genset power rating with fan @ 0.8 power factor 320 ekW280 ekW
100% load with fan, L/hr (gal/hr) 81.6 (21.5)70.8 (18.7)
75% load with fan, L/hr (gal/hr) 60.6 (16)53.5 (14.1)
50% load with fan, L/hr (gal/hr) 42.7 (11.2)38.2 (10.1)
25% load with fan, L/hr (gal/hr) 25.6 (6.7)23.2 (6.1)
Radiator air flow restriction (system), kPa (in. water) 0.12 (0.48)0.12 (0.48)
Radiator air flow, m3/min (CFM) 398 (14055)398 (14055)
Engine coolant capacity, L (gal) 13.9 (3.7)13.9 (3.7)
Radiator coolant capacity, L (gal) 43 (11.5)43 (11.5)
Total coolant capacity, L (gal) 56.9 (15.2)56.9 (15.2)
Combustion air inlet flow rate, m³/min (CFM) 22.4 (790)20.3 (717.5)
Max. Allowable Combustion Air Inlet Temp, °C (°F) 44 (110)44 (110)
Exhaust stack gas temperature, °C (°F) 529.2 (985)504.3 (939.7)
Exhaust gas flow rate, m³/min (CFM) 62.8 (2216)54.8 (1936.6)
Exhaust system backpressure (maximum allowable), kPa (in water) 10.0 (40.0)10.0 (40.0)
Heat rejection to jacket water, kW (BTU/min) 128 (7271)113 (6453)
Heat rejection to exhaust (total) kW (BTU/min) 290 (16484)249 (14146)
Heat rejection to aftercooler, kW (BTU/min) 54 (3037)43 (2425)
Heat rejection to atmosphere from engine, kW (BTU/min) 53 (3031)47 (2694)
NOx, mg/Nm³ (g/hp-hr) 2731 (5.3)2874.9 (5.6)
CO, mg/Nm³ (g/hp-hr) 750 (1.47)761.4 (1.5)
HC, mg/Nm³ (g/hp-hr) 8 (0.02)7.2 (0.02)
Voltages 415V400V380V
Motor starting capability @ 30% Voltage Dip 1071 skVA793 skVA888 skVA
Temperature Rise 125°C125°C125°C

Weights and Dimensions

Length
3,830 mm (151 in)
Width
1,130 mm (44 in)
Height
2,156 mm (85 in)
Weight
3,253 kg (7,172 lb)
Details

Note: General configuration not to be used for installation. See general dimension drawings for detail.

Applicable Codes and Standards

Details
AS1359, IEC60034-1, ISO 3046, ISO 8528, NEMA MG1-33, EAC, CE, UKCA. 1
ekW with 10% overload capability for emergency use for a maximum of 1 hour in 12. 3

Commercial Application

Standby and prime power for buildings, manufacturing, data centers and distributed infrastructure. The card helps quickly verify configuration, frequency, power, dimensions and delivery availability for a specific site.