Skip to content

Cat D400 GC diesel generator set

Full Technical Information

Open PDF Specification

Overview, Engine and Ratings

Bore x Stroke
130 mm x 157 mm (5.1 in x 6.2 in)
Displacement
12.5 L (763 in³)
Compression Ratio
16.3:1
Governor
Electronic ADEM™ A4 - G2 Class* capable

Package Performance

Details
Performance Standby
Frequency 60 Hz
Genset Power Rating 500 kVA
Genset power rating with fan @ 0.8 power factor 400 ekW
Emissions EPA TIER 3
100% load with fan, L/hr (gal/hr) 105.8 (27.9)
75% load with fan, L/hr (gal/hr) 90.7 (24.0)
50% load with fan, L/hr (gal/hr) 66.2 (17.5)
25% load with fan, L/hr (gal/hr) 37.7 (10.0)
Radiator air flow restriction (system), kPa (in. water) 0.12 (0.48)
Radiator air flow, m3/min (CFM) 398 (14055)
Engine coolant capacity, L (gal) 66.2 (17.5)
Radiator coolant capacity, L (gal) 37.7 (10)
Total coolant capacity, L (gal) 104 (27.5)
Combustion air inlet flow rate, m3/min (CFM) 24.4 (862)
Max. Allowable Combustion Air Inlet Temp, °C (°F) 47 (116)
Exhaust stack gas temperature, °C (°F) 567 (1053)
Exhaust gas flow rate, m³/min (CFM) 82 (2896)
Exhaust system backpressure (maximum allowable) kPa (in. water) 10 (40)
Heat rejection to jacket water, kW (BTU/min) 156 (8871)
Heat rejection to exhaust (total), kW (BTU/min) 398 (22634)
Heat rejection to aftercooler, kW (BTU/min) 71 (4037)
Heat rejection to atmosphere from engine, kW (BTU/min) 52 (2957)
Heat rejection from alternator, kW (BTU/min) 29 (1649)
NOx, mg/Nm³ (g/hp-hr) 2274.7 (4.58)
CO, mg/Nm³ (g/hp-hr) 666.9 (1.35)
HC, mg/Nm³ (g/hp-hr) 6.2 (0.01)
PM, mg/Nm³ (g/hp-hr) 39.4 (0.10)
LEHE2009-09 1/2
Voltages 480V600V
Motor starting capability @ 30% Voltage Dip, skVA 871731
Current, Amps 601.4481.1
Temperature Rise, °C 105130

Weights and Dimensions

Length
4,625 mm (182.8 in)
Width
1,630 mm (64.2 in)
Height
2,039 mm (80.3 in)
Weight
3,325 kg (7,330 lb)
Details

Note: General configuration not to be used for installation. See general dimension drawings for detail.

Applicable Codes and Standards

Details
CSA C22.2 No 100-04, UL142, UL489, UL869, cUL/UL2200, NFPA 37, NFPA 70, 1
normal source power. Average power output is 70% of the standby power rating. 2 diesel fuel with 35° API and LHV of 18,390 BTU/lb. The nominal emissions data

Commercial Application

Standby and prime power for buildings, manufacturing, data centers and distributed infrastructure. The card helps quickly verify configuration, frequency, power, dimensions and delivery availability for a specific site.