Cat C7.1 | DE165E0 diesel generator set

Power Ratings

RatingkVAekW
Standby165 kVA132 ekW
Prime150 kVA120 ekW

Full Technical Information

Open PDF Specification

Overview, Engine and Ratings

Bore x Stroke
105.0mm x 135.0mm (4.1in x 5.3 in)
Displacement
7.0 L (427.8 in³)
Compression Ratio
16.0:1

Package Performance

Details
Performance 50 Hz60 Hz
Gross Engine Power: kW (hp) 149.1 (200.0)136.0 (182.0)171.8 (230.0)155.4 (208.0)
Regenerative Power: kW 6.77.7
Combustion Air Flow: m³/min (cfm) 10.7 (377)10.0 (354)15.0 (529)14.4 (509)
Max. Combustion Air intake restriction: kPa (in H2O) 3.0 (12.0)
Radiator Cooling Air flow: m³/min (cfm) 303.4 (10714)239.4 (8454)
External Restriction to Cooling Air Flow: Pa (in H2O) 125 (0.5)
Heat Rejected to Water & Lube Oil: kW (Btu/min) 75.7 (4305)69.1 (3930)80.1 (4555)73.5 (4180)
Heat Radiated from Engine & Alternator: kW (Btu/min) 22.3 (1268)20.0 (1137)25.0 (1422)22.6 (1285)
Cooling System Capacity: l (US gal) 21.0 (5.5)
LEHE1149-01-ISO3046 1/3
Exhaust Gas Flow: m³/min (cfm) 25.5 (902)23.9 (843)32.2 (1137)31.9 (1125)
Exhaust Gas Temperature: °C (°F) 484 (903)484 (903)407 (765)407 (765)
Max. Allowable Back Pressure: kPa (in. Hg) 6.0 (1.8)6.0 (1.8)
50 Hz 60 Hz
Voltage 415/240V 230/115V220/127V
Motor Starting Capability* kVA 232218194261211161187195
Short Circuit Capacity** % 300300300300300300300300

Generator Technical Data

Weight: kg (lb)
Dimensions: mm (in)
Contact your local Cat dealer for power ratings at specific site conditions.
cannot exceed 25 hours per year.
0 power factor and shunt excitation system. **With optional Auxiliary winding.
25°C (77°F) air inlet temp, 100m (328ft) A.S.L. 30% relative humidity.

Commercial Application

Standby and prime power for buildings, manufacturing, data centers and distributed infrastructure. The card helps quickly verify configuration, frequency, power, dimensions and delivery availability for a specific site.