Power Ratings
| Rating | kVA | ekW |
|---|---|---|
| Rating 1 | 110 kVA | 88 ekW |
| Rating 2 | 100 kVA | 80 ekW |
Full Technical Information
Open PDF SpecificationOverview, Engine and Ratings
- Bore x Stroke
- 105.0mm x 127.0mm (4.1in x 5.0 in)
- Displacement
- 4.4 L (268.4 in³)
- Compression Ratio
- 16.7:1
- Governor
- Electronic
- 110.0 kVA (88.0 kW)
- 100.0 kVA (80.0 kW)
Package Performance
Details
Performance
StandbyPrime
Frequency
50 Hz50 Hz
Genset Power Rating
110.0 kVA100.0 kVA
Genset power rating with fan @ 0.8 power factor
88.0 kW80.0 kW
Fuel Tank Capacity, litres (US gal)
250 (66.0)
100% load with fan, L/hr (gal/hr)
24.7 (6.5)23.4 (6.2)
75% load with fan, L/hr (gal/hr)
20.7 (5.5)19.5 (5.2)
50% load with fan, L/hr (gal/hr)
15.6 (4.1)14.5 (3.8)
Radiator air flow restriction (system), kPa (in. Water)
5.0 (20.1)
Radiator air flow, m³/min (cfm)
201.0 (7098)
Total coolant capacity, L (gal)
17.0 (4.5)
Combustion air inlet flow rate, m³/min (cfm)
6.7 (238)6.4 (227)
Max. Allowable Combustion Air Inlet Temp, °C (°F)
50 (122)
Exhaust stack gas temperature, °C (°F)
675 (1247)657 (1215)
Exhaust gas flow rate, m³/min (cfm)
17.4 (614)16.4 (580)
Exhaust system backpressure (maximum allowable), kPa (in. water)
15.0 (4.4)
Heat rejection to jacket water, kW (Btu/min)
51.9 (2952)47.1 (2679)
Heat rejection to alternator, kW (Btu/min)
8.7 (495)
Heat rejection to atmosphere from engine, kW (Btu/min)
23.0 (1308)20.2 (1149)
LEHE1122-01
1/2
Voltages
415V400V380V
Motor starting capability @ 30% Voltage Dip, skVA
189168168
Current, amps
153159167
Temperature Rise, °C
163/27
Weights and Dimensions
- Length
- 2,089 mm (82.2 in)
- Width
- 1,120 mm (44.1 in)
- Height
- 1,495 mm (58.9 in)
- Weight
- 1,324 kg (2,919 lb)
Details
Note: General configuration not to be used for installation. See general dimension drawings for detail.
Applicable Codes and Standards
Details
AS1359, CSA C22.2 No100-04, UL142, UL489, UL869, UL2200, NFPA37, NFPA70,
1
MG1-33, 2006/95/EC, 2006/42/EC, 2004/108/EC.
2
of the normal source power. Average power output is 70% of the standby power
nominal emissions data shown is subject to instrumentation, measurement,
rating. Typical operation is 200 hours per year, with maximum expected usage of
facility and engine to engine variations. Emissions data is based on 100% load
output is 70% of the prime power rating. Typical peak demand is 100% of prime
3
hour in 12. Overload operation cannot exceed 25 hours per year
is based on a 40° C ambient per NEMA MG1-32.
Commercial Application