Skip to content

Cat C4.4 Marine Generator Sets

Power Ratings

RatingkVAekW
Rating 1110 kVA88 ekW
Rating 2100 kVA80 ekW

Full Technical Information

Open PDF Specification

Overview, Engine and Ratings

Bore x Stroke
105.0mm x 127.0mm (4.1in x 5.0 in)
Displacement
4.4 L (268.4 in³)
Compression Ratio
16.7:1
Governor
Electronic
110.0 kVA (88.0 kW)
100.0 kVA (80.0 kW)

Package Performance

Details
Performance StandbyPrime
Frequency 50 Hz50 Hz
Genset Power Rating 110.0 kVA100.0 kVA
Genset power rating with fan @ 0.8 power factor 88.0 kW80.0 kW
Fuel Tank Capacity, litres (US gal) 250 (66.0)
100% load with fan, L/hr (gal/hr) 24.7 (6.5)23.4 (6.2)
75% load with fan, L/hr (gal/hr) 20.7 (5.5)19.5 (5.2)
50% load with fan, L/hr (gal/hr) 15.6 (4.1)14.5 (3.8)
Radiator air flow restriction (system), kPa (in. Water) 5.0 (20.1)
Radiator air flow, m³/min (cfm) 201.0 (7098)
Total coolant capacity, L (gal) 17.0 (4.5)
Combustion air inlet flow rate, m³/min (cfm) 6.7 (238)6.4 (227)
Max. Allowable Combustion Air Inlet Temp, °C (°F) 50 (122)
Exhaust stack gas temperature, °C (°F) 675 (1247)657 (1215)
Exhaust gas flow rate, m³/min (cfm) 17.4 (614)16.4 (580)
Exhaust system backpressure (maximum allowable), kPa (in. water) 15.0 (4.4)
Heat rejection to jacket water, kW (Btu/min) 51.9 (2952)47.1 (2679)
Heat rejection to alternator, kW (Btu/min) 8.7 (495)
Heat rejection to atmosphere from engine, kW (Btu/min) 23.0 (1308)20.2 (1149)
LEHE1122-01 1/2
Voltages 415V400V380V
Motor starting capability @ 30% Voltage Dip, skVA 189168168
Current, amps 153159167
Temperature Rise, °C 163/27

Weights and Dimensions

Length
2,089 mm (82.2 in)
Width
1,120 mm (44.1 in)
Height
1,495 mm (58.9 in)
Weight
1,324 kg (2,919 lb)
Details

Note: General configuration not to be used for installation. See general dimension drawings for detail.

Applicable Codes and Standards

Details
AS1359, CSA C22.2 No100-04, UL142, UL489, UL869, UL2200, NFPA37, NFPA70, 1
MG1-33, 2006/95/EC, 2006/42/EC, 2004/108/EC. 2
of the normal source power. Average power output is 70% of the standby power nominal emissions data shown is subject to instrumentation, measurement,
rating. Typical operation is 200 hours per year, with maximum expected usage of facility and engine to engine variations. Emissions data is based on 100% load
output is 70% of the prime power rating. Typical peak demand is 100% of prime 3
hour in 12. Overload operation cannot exceed 25 hours per year is based on a 40° C ambient per NEMA MG1-32.

Commercial Application

Port and shore infrastructure, continuous power and heavy-duty operating profiles. The card helps quickly verify configuration, frequency, power, dimensions and delivery availability for a specific site.