Skip to content

Cat C4.4 | DE110E2 diesel generator set

Power Ratings

RatingkVAekW
Rating 1110 kVA88 ekW
Rating 2125 kVA100 ekW
Rating 3100 kVA80 ekW
Rating 4113 kVA90 ekW

Full Technical Information

Open PDF Specification

Overview, Engine and Ratings

Bore x Stroke
105.0 mm x 127.0 mm (4.1 in x 5.0 in)
Displacement
4.4 L (268.5 in³)
Compression Ratio
18.3:1
Governor
Electronic

Package Performance

Details
Performance StandbyPrime
Frequency 50 Hz60 Hz50 Hz60 Hz
Genset Power Rating 110 kVA125 kVA100 kVA113 kVA
Genset power rating with fan @ 0.8 power factor 88 ekW100 ekW80 ekW90 ekW
Fuel Tank Capacity, litres (US gal) 250 (66.0)
100% load with fan, L/hr (gal/hr) 23.8 (6.3)28.5 (7.5)21.7 (5.7)25.7 (6.8)
75% load with fan, L/hr (gal/hr) 18.0 (4.8)21.5 (5.7)16.5 (4.4)19.6 (5.2)
50% load with fan, L/hr (gal/hr) 12.6 (3.3)15.2 (4.0)11.7 (3.1)14.1 (3.7)
Radiator air flow, m³/min (CFM) 187.8 (6632)244.2 (8624)187.8 (6632)244.2 (8624)
Total coolant capacity, L (gal) 17.5 (4.6)
Max. Combustion Air Intake Restriction, kPa (in water) 8.0 (32.1)
Combustion air inlet flow rate, m³/min (CFM) 6.3 (221)7.8 (275)6.0 (212)7.8 (274)
Max. Allowable Combustion Air Inlet Temp, °C (°F) 50 (122)
Exhaust stack gas temperature, °C (°F) 543 (1009)574 (1065)514 (957)517 (963)
Exhaust gas flow rate, m³/min (CFM) 16.3 (576)20.4 (720)15.2 (537)18.4 (650)
Exhaust system backpressure (maximum allowable), kPa (in water) 18.0 (72.3)15.0 (60.2)18.0 (72.3)15.0 (60.2)
Heat rejection to jacket water, kW (BTU/min) 50.7 (2883)64.0 (3640)46.1 (2622)57.7 (3281)
Heat rejection to alternator, kW (BTU/min) 7.8 (444)8.3 (472)7.8 (444)8.3 (472)
Heat rejection to atmosphere from engine, kW (BTU/min) 15.3 (870)17.7 (1007)13.7 (779)15.7 (893)
LEHE0706-06 1/2
Duty Cycle StandbyPrime
Phase 3-Phase3-Phase
Voltages, V 200/115220/127380/220400/230415/240200/115220/127380/220400/230415/240
Current, Amps 318289167159153289262152144139
Temperature Rise, @ 40°C 163163163163163125125125125125
Temperature Rise @ 40°C 163163163163163163163163
Voltages, V 208/120 220/127 220/110 240/139 240/120 380/220 440/254 480/277 208/120 220/127 220/110 240/139 240/120 380/220 440/254 480/277
Current, Amps 347328328300.7300.7189.9164150.4313.7296.5296.5271.8271.8171.7148.3135.9

Weights and Dimensions

Length
2,089 mm (82.2 in)
Width
1,120 mm (44.1 in)
Height
1,375 mm (54.1 in)
Weight
1,129 kg (2,490 lb)
Details

Note: General configuration not to be used for installation. See general dimension drawings for detail.

Applicable Codes and Standards

Details
AS1359, IEC60034-1, ISO 3046, ISO 8528, NEMA MG1-33, EAC, CE, UKCA. 1

Commercial Application

Standby and prime power for buildings, manufacturing, data centers and distributed infrastructure. The card helps quickly verify configuration, frequency, power, dimensions and delivery availability for a specific site.