Cat C32B | 1500 kVA diesel generator set

Power Ratings

RatingkVAekW
Standby1,400 kVA1,120 ekW
Mission Critical1,400 kVA1,120 ekW
Prime1,275 kVA1,020 ekW

Full Technical Information

Open PDF Specification

Overview, Engine and Ratings

Bore – mm (in)
145 (5.7)
Stroke – mm (in)
162 (6.4)
Displacement – L (in³)
32.1 (1959)
Compression Ratio
14.0:1
Aspiration
TA
Governor Type
ADEM™ A4

Package Performance

Details
Performance StandbyMission CriticalPrime (req SRR)
Frequency 50 Hz50 Hz50 Hz
Gen set power rating with fan 1200 ekW1200 ekW1100 ekW
Gen set power rating with fan @ 0.8 power factor 1500 kVA1500 kVA1375 kVA
Emissions Low FuelLow FuelLow Fuel
100% load with fan – L/hr (gal/hr) 306.2 (80.8)306.2 (80.8)279.1 (73.7)
75% load with fan – L/hr (gal/hr) 226.4 (59.8)226.4 (59.8)207.8 (54.8)
50% load with fan – L/hr (gal/hr) 154.2 (40.7)154.2 (40.7)143.0 (37.7)
25% load with fan – L/hr (gal/hr) 89.8 (23.7)89.8 (23.7)84.2 (22.2)
Radiator air flow restriction (system) – kPa (in. water) 0.12 (0.48)0.12 (0.48)0.12 (0.48)
Radiator air flow – m³/min (CFM) 135513551355
Engine coolant capacity – L (gal) 55.0 (14.5)55.0 (14.5)55.0 (14.5)
Radiator coolant capacity – L (gal) 55.0 (14.5)55.0 (14.5)55.0 (14.5)
Total coolant capacity – L (gal) 110.0 (29.0)110.0 (29.0)110.0 (29.0)
Combustion air inlet flow rate – m³/min (CFM) 100.6 (3551.3)100.6 (3551.3)94.3 (3328.6)
Exhaust stack gas temperature – °C (°F) 429.6 (805.2)429.6 (805.2)424.0 (795.1)
Exhaust system backpressure (maximum allowable) – kPa (in. water) 6.7 (27.0)6.7 (27.0)6.7 (27.0)
Heat rejection to jacket water – kW (BTU/min) 385385376
Heat rejection to exhaust (total) – kW (BTU/min) 10671067956
Heat rejection to aftercooler – kW (BTU/min) 386386331
Heat rejection to atmosphere from engine – kW (BTU/min) 211211192
Heat rejection from alternator – kW (BTU/min) 57.957.951.8
NOx mg/Nm³ (g/hp-h) 2657.4 (5.14)2657.4 (5.14)2,633.8 (5.08)
CO mg/Nm³ (g/hp-h) 48.1 (0.13)48.1 (0.13)72.0 (0.15)
HC mg/Nm³ (g/hp-h) 6.3 (0.02)6.3 (0.02)8.0 (0.02)
PM mg/Nm³ (g/hp-h) 6.9 (0.02)6.9 (0.02)6.5 (0.02)
NOx mg/Nm³ (g/hp-h) 3215.5 (6.21)3215.5 (6.21)3,186.9 (6.15)
CO mg/Nm³ (g/hp-h) 90.0 (0.23)90.0 (0.23)134.6 (0.29)
HC mg/Nm³ (g/hp-h) 11.8 (0.03)11.8 (0.03)15.1 (0.04)
PM mg/Nm³ (g/hp-h) 13.5 (0.03)13.5 (0.03)12.7 (0.03)

Weights and Dimensions

Length
1,400 mm (1,120 in)
Width
1,400 mm (1,120 in)
Height
1,275 mm (1,020 in)
Weight
4,385 kg (173 lb)
Details

Note: For reference only. Do not use for installation design. Contact your account manager for precise weights and dimensions.

Ratings and Definitions

Details
interruption of the normal source power. Average power output is 70% of the CSA C22.2 No 100-04, UL489, UL 2200, IBC, IEC 60034-1, ISO 3046,
standby power rating. Typical operation is 200 hours per year, with maximum ISO 8528, NEMA MG1-22, NEMA MG1-33, and facilitates compliance to
is 100% of prime rated ekW with 10% overload capability for emergency use All ratings ANSI/TIA-942 compliant for Rated-1 through
for a maximum of 1 hour in 12.Overload operation cannot exceed 25 hours per Rated-4 data centers.

Commercial Application

Standby and prime power for buildings, manufacturing, data centers and distributed infrastructure. The card helps quickly verify configuration, frequency, power, dimensions and delivery availability for a specific site.