Cat C32B | 1500 kVA diesel generator set
Power Ratings
| Rating | kVA | ekW |
|---|---|---|
| Standby | 1,400 kVA | 1,120 ekW |
| Mission Critical | 1,400 kVA | 1,120 ekW |
| Prime | 1,275 kVA | 1,020 ekW |
Full Technical Information
Open PDF SpecificationOverview, Engine and Ratings
- Bore – mm (in)
- 145 (5.7)
- Stroke – mm (in)
- 162 (6.4)
- Displacement – L (in³)
- 32.1 (1959)
- Compression Ratio
- 14.0:1
- Aspiration
- TA
- Governor Type
- ADEM™ A4
Package Performance
Details
Performance
StandbyMission CriticalPrime (req SRR)
Frequency
50 Hz50 Hz50 Hz
Gen set power rating with fan
1200 ekW1200 ekW1100 ekW
Gen set power rating with fan @ 0.8 power factor
1500 kVA1500 kVA1375 kVA
Emissions
Low FuelLow FuelLow Fuel
100% load with fan – L/hr (gal/hr)
306.2 (80.8)306.2 (80.8)279.1 (73.7)
75% load with fan – L/hr (gal/hr)
226.4 (59.8)226.4 (59.8)207.8 (54.8)
50% load with fan – L/hr (gal/hr)
154.2 (40.7)154.2 (40.7)143.0 (37.7)
25% load with fan – L/hr (gal/hr)
89.8 (23.7)89.8 (23.7)84.2 (22.2)
Radiator air flow restriction (system) – kPa (in. water)
0.12 (0.48)0.12 (0.48)0.12 (0.48)
Radiator air flow – m³/min (CFM)
135513551355
Engine coolant capacity – L (gal)
55.0 (14.5)55.0 (14.5)55.0 (14.5)
Radiator coolant capacity – L (gal)
55.0 (14.5)55.0 (14.5)55.0 (14.5)
Total coolant capacity – L (gal)
110.0 (29.0)110.0 (29.0)110.0 (29.0)
Combustion air inlet flow rate – m³/min (CFM)
100.6 (3551.3)100.6 (3551.3)94.3 (3328.6)
Exhaust stack gas temperature – °C (°F)
429.6 (805.2)429.6 (805.2)424.0 (795.1)
Exhaust system backpressure (maximum allowable) – kPa (in. water)
6.7 (27.0)6.7 (27.0)6.7 (27.0)
Heat rejection to jacket water – kW (BTU/min)
385385376
Heat rejection to exhaust (total) – kW (BTU/min)
10671067956
Heat rejection to aftercooler – kW (BTU/min)
386386331
Heat rejection to atmosphere from engine – kW (BTU/min)
211211192
Heat rejection from alternator – kW (BTU/min)
57.957.951.8
NOx mg/Nm³ (g/hp-h)
2657.4 (5.14)2657.4 (5.14)2,633.8 (5.08)
CO mg/Nm³ (g/hp-h)
48.1 (0.13)48.1 (0.13)72.0 (0.15)
HC mg/Nm³ (g/hp-h)
6.3 (0.02)6.3 (0.02)8.0 (0.02)
PM mg/Nm³ (g/hp-h)
6.9 (0.02)6.9 (0.02)6.5 (0.02)
NOx mg/Nm³ (g/hp-h)
3215.5 (6.21)3215.5 (6.21)3,186.9 (6.15)
CO mg/Nm³ (g/hp-h)
90.0 (0.23)90.0 (0.23)134.6 (0.29)
HC mg/Nm³ (g/hp-h)
11.8 (0.03)11.8 (0.03)15.1 (0.04)
PM mg/Nm³ (g/hp-h)
13.5 (0.03)13.5 (0.03)12.7 (0.03)
Weights and Dimensions
- Length
- 1,400 mm (1,120 in)
- Width
- 1,400 mm (1,120 in)
- Height
- 1,275 mm (1,020 in)
- Weight
- 4,385 kg (173 lb)
Details
Note: For reference only. Do not use for installation design. Contact your account manager for precise weights and dimensions.
Ratings and Definitions
Details
interruption of the normal source power. Average power output is 70% of the
CSA C22.2 No 100-04, UL489, UL 2200, IBC, IEC 60034-1, ISO 3046,
standby power rating. Typical operation is 200 hours per year, with maximum
ISO 8528, NEMA MG1-22, NEMA MG1-33, and facilitates compliance to
is 100% of prime rated ekW with 10% overload capability for emergency use
All ratings ANSI/TIA-942 compliant for Rated-1 through
for a maximum of 1 hour in 12.Overload operation cannot exceed 25 hours per
Rated-4 data centers.
Commercial Application
Standby and prime power for buildings, manufacturing, data centers and distributed infrastructure. The card helps quickly verify configuration, frequency, power, dimensions and delivery availability for a specific site.