Cat C32 High Performance Propulsion Engines
Power Ratings
| Rating | kVA | ekW |
|---|---|---|
| Standby | 1,100 kVA | 880 ekW |
| Mission Critical | 1,100 kVA | 880 ekW |
| Prime | 1,000 kVA | 800 ekW |
| Continuous | 910 kVA | 728 ekW |
Full Technical Information
Open PDF SpecificationOverview, Engine and Ratings
- Bore – mm (in)
- 145 (5.7)
- Stroke – mm (in)
- 162 (6.4)
- Displacement – L (in3)
- 32 (1952.76)
- Compression Ratio
- 15.0:1
- Aspiration
- TA
- Governor Type
- ADEM™ A4
Package Performance
Details
Performance
StandbyMission CriticalPrime
Frequency
50 Hz50 Hz50 Hz
Gen set power rating with fan
1000 ekW1000 ekW880 ekW
Gen set power rating with fan @ 0.8 power factor
1250 kVA1250 kVA1100 kVA
100% load with fan – L/hr (gal/hr)
252.3 (66.7)252.3 (66.7)220.7 (58.3)
75% load with fan – L/hr (gal/hr)
185.5 (49.0)185.5 (49.0)164.8 (43.5)
50% load with fan – L/hr (gal/hr)
128.4 (33.9)128.4 (33.9)116.1 (30.7)
25% load with fan – L/hr (gal/hr)
75.0 (19.8)75.0 (19.8)68.7 (18.1)
Radiator air flow restriction (system) – kPa (in. water)
0.12 (0.48)0.12 (0.48)0.12 (0.48)
Radiator air flow – m3/min (cfm)
825825825
Engine coolant capacity – L (gal)
55 (14.5)55 (14.5)55 (14.5)
Radiator coolant capacity – L (gal)
171 (45.0)171 (45.0)171 (45.0)
Total coolant capacity – L (gal)
226 (59.5)226 (59.5)226 (59.5)
Combustion air inlet flow rate – m3/min (cfm)
74.2 (2619.0)74.2 (2619.0)67.9 (2397.4)
Exhaust stack gas temperature – °C (°F)
464.6 (868.3)464.6 (868.3)440.6 (825.2)
Exhaust gas flow rate – m3/min (cfm)
192.9 (6812.8)192.9 (6812.8)170.3 (6012.6)
Heat rejection to jacket water – kW (Btu/min)
340340308
Heat rejection to exhaust (total) – kW (Btu/min)
871871752
Heat rejection to aftercooler – kW (Btu/min)
241241196
Heat rejection from alternator – kW (Btu/min)
525243
NOx mg/Nm3 (g/hp-h)
2928.1 (5.80)2928.1 (5.80)3185.5 (6.15)
CO mg/Nm3 (g/hp-h)
229.6 (0.46)229.6 (0.46)209.4 (0.42)
PM mg/Nm3 (g/hp-h)
11.9 (0.03)11.9 (0.03)11.3 (0.03)
NOx mg/Nm3 (g/hp-h)
3543.0 (7.02)3543.0 (7.02)3854.5 (7.45)
HC mg/Nm3 (g/hp-h)
10.7 (0.02)10.7 (0.02)10.5 (0.02)
Weights and Dimensions
- Length
- 1,100 mm (880 in)
- Width
- 1,100 mm (880 in)
- Height
- 1,000 mm (800 in)
- Weight
- 910 kg (728 lb)
Details
Note: For reference only. Do not use for installation design. Contact your account manager for precise weights and dimensions.
Ratings and Definitions
- Standby
- Output available with varying load for the duration of the interruption of the normal source power. Average power output is 70% of the standby power rating. Typical operation is 200 hours per year, with maximum expected usage of 500 hours per year.
- Mission Critical
- Output available with varying load for the duration of the interruption of the normal source power. Average power output is 85% of the mission critical power rating. Typical peak demand up to 100% of rated power for up to 5% of the operating time. Typical operation is 200 hours per year, with maximum expected usage of 500 hours per year.
- Prime
- Output available with varying load for an unlimited time. Average power output is 70% of the prime power rating. Typical peak demand is 100% of prime rated ekW with 10% overload capability for emergency use for a maximum of 1 hour in 12. Overload operation cannot exceed 25 hours per year.
- Continuous
- Output available with non-varying load for an unlimited time. Average power output is 70-100% of the continuous power rating. Typical peak demand is 100% of continuous rated kW for 100% of the operating hours. C32-PGCG LEHE1263-00 (4-17)
Commercial Application
Port and shore infrastructure, continuous power and heavy-duty operating profiles. The card helps quickly verify configuration, frequency, power, dimensions and delivery availability for a specific site.