Cat C3.3 | DE33E0 diesel generator set
Full Technical Information
Open PDF SpecificationOverview, Engine and Ratings
- Bore x Stroke
- 105.0mm x 127.0mm (4.1in x 5.0 in)
- Displacement
- 3.3 L (201.4 in³)
- Compression Ratio
- 19.25:1
Package Performance
Details
Performance
StandbyPrime
50 Hz
60 Hz50 Hz60 Hz
Frequency
50 Hz60 Hz50 Hz60 Hz
Genset Power Rating
33.0 kVA37.5 kVA30.0 kVA33.8 kVA
Genset power rating with fan @ 0.8 power factor
26.4 kW30.0 kW24.0 kW27.0 kW
Fuel Tank Capacity, litres (US gal)
161 (42.5)
100% load with fan, L/hr (gal/hr)
7.7 (2.0)9.1 (2.4)6.9 (1.8)8.1 (2.1)
75% load with fan, L/hr (gal/hr)
5.7 (1.5)6.8 (1.8)5.2 (1.4)6.2 (1.6)
50% load with fan, L/hr (gal/hr)
4.1 (1.1)5.0 (1.3)3.8 (1.0)4.7 (1.2)
Radiator air flow restriction (system), kPa (in. Water)
6.5 (26.1)
Radiator air flow, m³/min (cfm)
62.6 (2211)84.8 (2995)62.6 (2211)84.8 (2995)
Total coolant capacity, L (gal)
10.2 (2.7)
Combustion air inlet flow rate, m³/min (cfm)
2.2 (76)2.6 (91)2.2 (76)2.6 (92)
Max. Allowable Combustion Air Inlet Temp, °C (°F)
50 (122)
Exhaust stack gas temperature, °C (°F)
520 (968)530 (986)500 (932)520 (968)
Exhaust gas flow rate, m³/min (cfm)
5.8 (205)6.6 (233)5.7 (201)6.4 (226)
Exhaust system backpressure (maximum allowable), kPa (in. water)
8.0 (2.4)10.0 (3.0)8.0 (2.4)10.0 (3.0)
Heat rejection to jacket water, kW (Btu/min)
18.0 (1024)22.0 (1251)16.0 (910)18.0 (1024)
Heat rejection to alternator, kW (Btu/min)
3.8 (216)4.4 (250)3.8 (216)4.4 (250)
Heat rejection to atmosphere from engine, kW (Btu/min)
9.8 (557)10.4 (591)8.1 (461)8.8 (500)
LEHE1061-01
1/2
Voltages
415V400V380V220V480V380V240V440V
Current, amps
4648508745538949
Temperature Rise, °C
163/27163/27163/27163/27125/40163/27125/40163/27
Weights and Dimensions
- Length
- 1,540 mm (60.6 in)
- Width
- 970 mm (38.2 in)
- Height
- 1,361 mm (53.6 in)
- Weight
- 838 kg (1,847 lb)
Details
Note: General configuration not to be used for installation. See general dimension drawings for detail.
Applicable Codes and Standards
Details
AS1359, CSA C22.2 No100-04, UL142, UL489, UL869, UL2200, NFPA37, NFPA70,
1
MG1-33, 2006/95/EC, 2006/42/EC, 2004/108/EC.
2
of the normal source power. Average power output is 70% of the standby power
nominal emissions data shown is subject to instrumentation, measurement,
rating. Typical operation is 200 hours per year, with maximum expected usage of
facility and engine to engine variations. Emissions data is based on 100% load
output is 70% of the prime power rating. Typical peak demand is 100% of prime
3
hour in 12. Overload operation cannot exceed 25 hours per year
is based on a 40° C ambient per NEMA MG1-32.
Commercial Application
Standby and prime power for buildings, manufacturing, data centers and distributed infrastructure. The card helps quickly verify configuration, frequency, power, dimensions and delivery availability for a specific site.