Cat C2.2 | DE16E3S diesel generator set

Full Technical Information

Open PDF Specification

Overview, Engine and Ratings

Bore x Stroke
84 mm x 100 mm (3.3 in x 3.9 in)
Displacement
2.2 L (135.2 in³)
Compression Ratio
23.3:1

Package Performance

Details
Performance StandbyPrime
Frequency 50 Hz60 Hz50 Hz60 Hz
Genset Power Rating 16.5 kVA19.4 kVA15.0 kVA17.6 kVA
Genset power rating with fan @ 1.0 power factor 16.5 ekW19.4 ekW15.0 ekW17.6 ekW
110% load with fan, L/hr (gal/hr) NA5.5 (1.5)6.3 (1.7)
100% load with fan, L/hr (gal/hr) 5.5 (1.5)6.3 (1.7)4.9 (1.3)5.7 (1.5)
75% load with fan, L/hr (gal/hr) 4.0 (1.1)4.8 (1.3)3.7 (1.0)4.4 (1.2)
50% load with fan, L/hr (gal/hr) 2.9 (0.8)3.5 (0.9)2.7 (0.7)3.3 (0.9)
Radiator air flow restriction (system), kPa (in water) 0.5 (2)0.5 (2)0.5 (2)0.5 (2)
Radiator air flow, m³/min (CFM) 33 (1165)41.4 (1462)33 (1165)41.4 (1462)
Total coolant capacity, L (gal) 6.5 (1.7)6.5 (1.7)6.5 (1.7)6.5 (1.7)
Combustion air inlet flow rate, m³/min (CFM) 1.5 (51)1.7 (61)1.5 (51)1.7 (61)
Max. Allowable Combustion Air Inlet Temp, °C 50505050
Exhaust stack gas temperature, °C (°F) 505 (941)510 (950)445 (833)440 (824)
Exhaust gas flow rate, m³/min (CFM) 3.9 (139)4.8 (168)3.6 (129)4.3 (153)
Exhaust system backpressure (maximum allowable), kPa (in water) 10.2 (41)10.2 (41)10.2 (41)10.2 (41)
Heat rejection to jacket water, kW (BTU/min) 19.6 (1115)22.2 (1262)17.0 (967)19.9 (1132)
Heat rejection to atmosphere from engine & alternator, kW (BTU/min) 6.9 (392)7.7 (438)5.4 (307)6.4 (364)
Duty Cycle StandbyPrimeStandbyPrime
Phase 1-Phase1-Phase1-Phase1-Phase
Voltages, V 220/110230/115240/120220/110230/115240/120240/120240/120
Current, Amps 75726968656380.773.3
Temperature Rise, @ 40°C 163163163125125125163125
Temperature Rise @ 40°C 150150150125125125163125

Weights and Dimensions

Length
1,500 mm (59.1 in)
Width
620 mm (24.4 in)
Height
1,115 mm (43.9 in)
Weight
447 kg (985 lb)
Details

Note: General configuration not to be used for installation. See general dimension drawings for detail.

Applicable Codes and Standards

Details
AS1359, IEC60034-1, ISO 3046, ISO 8528, NEMA MG1-33, EAC, CE, UKCA. 1

Commercial Application

Standby and prime power for buildings, manufacturing, data centers and distributed infrastructure. The card helps quickly verify configuration, frequency, power, dimensions and delivery availability for a specific site.