Cat C18 diesel fire pump
Full Technical Information
Open PDF SpecificationOverview, Engine and Ratings
- Bore x Stroke
- 145 mm x 183 mm (5.71 in x 7.2 in)
- Displacement
- 18.13 L ( 1106.36 in3)
- Compression Ratio
- 14.5:1
- Governor
- Electronic ADEM™ A4
Package Performance
Details
Performance
StandbyPrime
Frequency
50 Hz50 Hz
Genset power rating
660 kVA600 kVA
Genset power rating with fan @ 0.8 power factor
528 ekW480 ekW
100% load with fan, L/hr (gal/hr)
135.0 (35.7)122.7 (32.4)
75% load with fan, L/hr (gal/hr)
100.9 (26.7)91.9 (24.3)
50% load with fan, L/hr (gal/hr)
69.5 (18.3)63.9 (16.9)
25% load with fan, L/hr (gal/hr)
40.1 (10.6)37.3 (9.8)
Radiator air flow restriction (system), kPa (in. water)
0.12 (0.48)0.12 (0.48)
Radiator air flow, m3/min (cfm)
645 (22778)645 (22778)
Engine coolant capacity, L (gal)
20.8 (5.5)20.8 (5.5)
Radiator coolant capacity, L (gal)
37.0 (9.7)37.0 (9.7)
Total coolant capacity, L (gal)
57.8 (15.2)37.0 (9.7)
Combustion air inlet flow rate, m³/min (cfm)
34.2 (1207)32.3 (1142.0)
Max. allowable combustion air inlet temp, °C (°F)
49 (120)49 (120)
Exhaust stack gas temperature, °C (°F)
N/A555.6 (1032.0)
Exhaust gas flow rate, m³/min (cfm)
102.4 (3616)94.3 (3329.2)
Exhaust system backpressure (maximum allowable) kPa (in. water)
10.0 (40.0)10.0 (40.0)
Heat rejection to jacket water, kW (Btu/min)
169 (9625)157 (8947)
Heat rejection to exhaust (total) kW (Btu/min)
504 (28661)458 (26037)
Heat rejection to aftercooler, kW (Btu/min)
91 (5186)79 (4475)
Heat rejection to atmosphere from engine, kW (Btu/min)
84 (4787)79 (4468)
NOx, mg/Nm³ (g/hp-hr)
3486.4 (7.0)3490.3 (6.9)
CO, mg/Nm³ (g/hp-hr)
507.4 (1.0)506.5 (1.0)
HC, mg/Nm³ (g/hp-hr)
1.7 (0.0)2.6 (0.0)
PM, mg/Nm³ (g/hp-hr)
4.7 (0.0)4.7 (0.0)
Voltages
380V380V
Motor starting capability @ 30% Voltage Dip, skVA
11631163
Current, amps
1003912
Temperature Rise, °C
150°C125°C
Weights and Dimensions
- Length
- 3,910 mm (154 in)
- Width
- 1,461 mm (58 in)
- Height
- 2,156 mm (85 in)
- Weight
- 4,114 kg (9,070 lb)
Details
Note: General configuration not to be used for installation. See general dimension drawings for detail.
Applicable Codes and Standards
Details
AS1359, CSA C22.2 No100-04, UL142, UL489, UL869, UL2200, NFPA37, NFPA70,
1
NEMA MG1-33, 2006/95/EC, 2006/42/EC, 2004/108/EC.
2
normal source power. Average power output is 70% of the standby power rating. Typical
data shown is subject to instrumentation, measurement, facility and engine to engine
ekW with 10% overload capability for emergency use for a maximum of 1 hour in 12.
rise and motor starting characteristics. Generator temperature rise is based on a 40°C
Commercial Application
Compact industrial sets, mobile applications, service sites and small facilities. The card helps quickly verify configuration, frequency, power, dimensions and delivery availability for a specific site.