Skip to content

Cat C18 diesel fire pump

Full Technical Information

Open PDF Specification

Overview, Engine and Ratings

Bore x Stroke
145 mm x 183 mm (5.71 in x 7.2 in)
Displacement
18.13 L ( 1106.36 in3)
Compression Ratio
14.5:1
Governor
Electronic ADEM™ A4

Package Performance

Details
Performance StandbyPrime
Frequency 50 Hz50 Hz
Genset power rating 660 kVA600 kVA
Genset power rating with fan @ 0.8 power factor 528 ekW480 ekW
100% load with fan, L/hr (gal/hr) 135.0 (35.7)122.7 (32.4)
75% load with fan, L/hr (gal/hr) 100.9 (26.7)91.9 (24.3)
50% load with fan, L/hr (gal/hr) 69.5 (18.3)63.9 (16.9)
25% load with fan, L/hr (gal/hr) 40.1 (10.6)37.3 (9.8)
Radiator air flow restriction (system), kPa (in. water) 0.12 (0.48)0.12 (0.48)
Radiator air flow, m3/min (cfm) 645 (22778)645 (22778)
Engine coolant capacity, L (gal) 20.8 (5.5)20.8 (5.5)
Radiator coolant capacity, L (gal) 37.0 (9.7)37.0 (9.7)
Total coolant capacity, L (gal) 57.8 (15.2)37.0 (9.7)
Combustion air inlet flow rate, m³/min (cfm) 34.2 (1207)32.3 (1142.0)
Max. allowable combustion air inlet temp, °C (°F) 49 (120)49 (120)
Exhaust stack gas temperature, °C (°F) N/A555.6 (1032.0)
Exhaust gas flow rate, m³/min (cfm) 102.4 (3616)94.3 (3329.2)
Exhaust system backpressure (maximum allowable) kPa (in. water) 10.0 (40.0)10.0 (40.0)
Heat rejection to jacket water, kW (Btu/min) 169 (9625)157 (8947)
Heat rejection to exhaust (total) kW (Btu/min) 504 (28661)458 (26037)
Heat rejection to aftercooler, kW (Btu/min) 91 (5186)79 (4475)
Heat rejection to atmosphere from engine, kW (Btu/min) 84 (4787)79 (4468)
NOx, mg/Nm³ (g/hp-hr) 3486.4 (7.0)3490.3 (6.9)
CO, mg/Nm³ (g/hp-hr) 507.4 (1.0)506.5 (1.0)
HC, mg/Nm³ (g/hp-hr) 1.7 (0.0)2.6 (0.0)
PM, mg/Nm³ (g/hp-hr) 4.7 (0.0)4.7 (0.0)
Voltages 380V380V
Motor starting capability @ 30% Voltage Dip, skVA 11631163
Current, amps 1003912
Temperature Rise, °C 150°C125°C

Weights and Dimensions

Length
3,910 mm (154 in)
Width
1,461 mm (58 in)
Height
2,156 mm (85 in)
Weight
4,114 kg (9,070 lb)
Details

Note: General configuration not to be used for installation. See general dimension drawings for detail.

Applicable Codes and Standards

Details
AS1359, CSA C22.2 No100-04, UL142, UL489, UL869, UL2200, NFPA37, NFPA70, 1
NEMA MG1-33, 2006/95/EC, 2006/42/EC, 2004/108/EC. 2
normal source power. Average power output is 70% of the standby power rating. Typical data shown is subject to instrumentation, measurement, facility and engine to engine
ekW with 10% overload capability for emergency use for a maximum of 1 hour in 12. rise and motor starting characteristics. Generator temperature rise is based on a 40°C

Commercial Application

Compact industrial sets, mobile applications, service sites and small facilities. The card helps quickly verify configuration, frequency, power, dimensions and delivery availability for a specific site.